Skip to main content
ABB 3ABD00057989-D — AC Drive (VFD) 480V

ABB 3ABD00057989-D ACS530-04-505A-4, 250 kW, 505 A

MPN3ABD00057989-D
Active

ABB ACS530-04-505A-4+N7569+B051+P974, 3-phase, 380-480 V, 250 kW, 505 A, IP00, Frame R10.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00057989-D — Power & Output
ParameterValue
Output power, normal duty250 kW
Output current, normal duty505 A
Output power, light overload250 kW
Output current, light overload485 A
Efficiency class (IE)IE2
3ABD00057989-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00057989-D — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeModule

Product details

The ABB 3ABD00057989-D is an ACS530-04 series drive rated for 250 kW normal-use output at 505 A, with a light-overload current of 485 A at the same power level. The unit is frame size R10, open type (IP00), and carries IE2 efficiency classification.

The 505 A normal-use current (In) is the continuous rating for a typical motor load; the 485 A light-overload figure (IlD) applies when the drive is sized for a slightly lower duty cycle. Both are at the same 250 kW output, so the overload headroom is minimal — if your application expects sustained overloads above 105% of In, consider a larger frame. The IP00 open-type enclosure means the drive is intended for installation inside a panel or cabinet that provides the environmental protection. Frame R10 is a physical size that determines mounting hole pattern and bus-bar spacing; verify cabinet cutout dimensions against the ABB mechanical drawing for this frame.

Frequently asked questions

What is the frame size of this drive?

The frame size is R10, which is a physical mounting and bus-bar standard for the ACS530-04 series at this power level.

What is the output power and current rating?

Normal-use output is 250 kW at 505 A; light-overload output is also 250 kW at 485 A.

MPN