Skip to main content
ABB 3ABD00058662-D — AC Drive (VFD) 480V

ABB 3ABD00058662-D ACQ531 Drive, 160 kW, 293 A, R8

MPN3ABD00058662-D
Active

ABB ACQ531-01-293A-4+P974, 3-phase 380-480 V, 160 kW normal use, 293 A, frame R8, IP20, wall-mounted.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00058662-D — Power & Output
ParameterValue
Output power, normal duty160 kW
Output current, normal duty293 A
Output power, light overload160 kW
Output current, light overload278 A
Efficiency class (IE)IE2

Input / Supply

3ABD00058662-D — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00058662-D — Mechanical & Cooling
ParameterValue
Frame sizeR8
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeWall-mounted

Product details

The ABB 3ABD00058662-D is an ACQ531-01-293A-4+P974 drive, rated 160 kW normal-use output with a continuous 293 A rating — sized for a 3-phase 380–480 V supply. Light-overload duty (160 kW, 278 A) matches the same power but draws less current, so the normal-use figure governs the thermal design of the output conductors. Frame R8 wall-mounted, IP20 enclosure; NEMA Open Type means it expects a clean, non-condensing environment.

The 293 A normal-use output current (In) is the figure to size the motor cable and input protection against — it is the continuous rating at the rated switching frequency. Light-overload IlD at 278 A gives a lower thermal load for the same power rating, useful when the application duty cycle stays below 100 %. The 47.5–63 Hz input frequency range covers 50/60 Hz grids without derating. IE2 efficiency level is standard for this generation; not premium, but within regulatory minimums for the power band.

Installation constraints

Wall-mount only — no floor-standing frame option. IP20 requires a clean, dry cabinet; NEMA Open Type means no drip shield or corrosion protection. Verify clearance above and below for airflow; the R8 frame dissipates heat through the baseplate, so the mounting surface must be non-combustible.

Frequently asked questions

What frame size is this drive?

R8 frame, wall-mounted.

What are the key output ratings?

Normal-use output: 160 kW at 293 A. Light-overload: 160 kW at 278 A. Input voltage 380–480 V, 3-phase, 47.5–63 Hz.

MPN