The 3ABD00059190-D: Frame size R1 keeps the footprint compact for a 1.5 kW drive. The 4 A normal-use rating matches a standard 1.5 kW induction motor on 400 V; the light-overload figure of 3.8 A is slightly lower, so if your load profile demands sustained overload capability, confirm the duty cycle against the motor nameplate. IE2 efficiency is the baseline for this class.
Installation notes
Wall-mount the unit with clearance for the IP20 enclosure — no conduit knockouts, so plan cable entry via glands or the bottom plate. The input range covers 380-480 V three-phase, common across global 400 V and 480 V grids.