The ABB 3ABD00059224-D is a drive rated for 500 kW normal-use output and 880 A normal-use current, built on a frame size R11 chassis. It takes 380-480 V three-phase input and covers 47.5 to 63 Hz line frequencies.
The 880 A normal-use current (In) decides the feeder breaker and cable size for continuous motor load at 500 kW. The light-overload rating is 865 A (IlD) at the same 500 kW.
Installation notes
IP00 means the drive has no internal protection against dust or accidental contact — it must live in a clean, locked cabinet with proper clearance for airflow. The open-type NEMA enclosure matches that same expectation: it's a chassis mount for a panel builder, not a standalone unit. On a 500 kW drive, that cabinet needs forced ventilation or air conditioning; the heat sink alone will reject several kW at full load. Verify the bus bar and cable lug sizes for 880 A before ordering — the frame R11 terminals are sized for large-gauge copper, not standard panel wire.