ABB 3ABD00059277-D — AC Drive (VFD) 600V

ABB 3ABD00059277-D ACS880-04 Drive Module, 710 kW, 721 A

MPN3ABD00059277-D
Active

ABB ACS880-04 series, LV AC industrial single drive module with position control, 710 kW normal-use output, 721 A, 525-690 V input, frame size R11, IP20 open type.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00059277-D — Identification
ParameterValue
Frame sizeR11
3ABD00059277-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range48 ... 63 Hz
3ABD00059277-D — Output / Performance
ParameterValue
Output power, normal duty710 kW
Output power, heavy duty560 kW
Output power, light overload630 kW
Output current, normal duty721 A
Output current, heavy duty571 A
Output current, light overload705 A
3ABD00059277-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00059277-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The ABB 3ABD00059277-D is an ACS880-04-series LV AC industrial single drive module with position control, rated for 710 kW normal-use output at 721 A on a 525-690 V three-phase supply. Frame size R11, IP20 open-type enclosure. This is the module variant — no cabinet, no line-side components — sized for integration into a larger drive system.

Three duty points are listed: normal use at 710 kW / 721 A, light-overload at 630 kW / 705 A, and heavy-duty at 560 kW / 571 A. The heavy-duty figure governs continuous operation on a constant-torque load like a conveyor or extruder — that 571 A is the current the module can sustain without tripping on a high-breakaway-torque application. The normal-use rating applies to variable-torque loads such as centrifugal pumps and fans where the current draw drops with speed. The light-overload curve sits between the two, useful for applications with occasional peak demands.

Integration notes

Mounts as a module — no enclosure, no line filter, no braking chopper included. Input voltage range of 525-690 V covers 690 V IEC networks and 600 V北美 systems; frequency range of 48-63 Hz handles both 50 Hz and 60 Hz supplies. The position control capability is built into the drive firmware, eliminating the need for a separate motion controller on applications like cut-to-length or indexing.

Frequently asked questions

What is the frame size of 3ABD00059277-D?

The frame size is R11. This is the physical size class for the module, determining mounting dimensions and busbar connections within the ACS880-04 family.

What are the heavy-duty and normal-use current ratings?

Normal-use output current is 721 A (710 kW), heavy-duty is 571 A (560 kW), and light-overload is 705 A (630 kW). The heavy-duty rating governs constant-torque loads; normal-use applies to variable-torque applications.

MPN