Skip to main content
ABB 3ABD00059299-D — AC Drive (VFD) 600V

3ABD00059299-D ACS880-04 Drive Module, 560 kW, 590 A, R11

MPN3ABD00059299-D
Active

ABB ACS880-04 single drive module, 560 kW / 590 A normal use, frame R11, 525-690 V 3-phase input, IP20 open type.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00059299-D — Identification
ParameterValue
Frame sizeR11
3ABD00059299-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3ABD00059299-D — Output / Performance
ParameterValue
Output power, normal duty560 kW
Output power, heavy duty500 kW
Output power, light overload560 kW
Output current, normal duty590 A
Output current, heavy duty505 A
Output current, light overload571 A
Efficiency level (IE class)IE2
3ABD00059299-D — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3ABD00059299-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

Drive module, sized for the line

This module (3ABD00059299-D) is a single LV AC industrial drive in frame R11, rated for 560 kW normal-use output at 590 A, with heavy-duty capability at 500 kW and 505 A. It takes a 525 to 690 V three-phase input and runs on 47.5 to 63 Hz mains.

Which rating fits your load

The drive carries three duty ratings. Normal use (Pn 560 kW, In 590 A) is for pumps and fans. Heavy-duty (PhD 500 kW, IhD 505 A) handles constant-torque loads like conveyors. Light-overload (PlD 560 kW, IlD 571 A) splits the difference.

Frame R11 is a module-style drive — bolts into the cabinet, not a standalone enclosure. The open-type NEMA rating matches: this lives inside a clean, dry panel. The 47.5 to 63 Hz input tolerance covers both 50 Hz and 60 Hz grids without adjustment.

Frequently asked questions

What is the frame size of 3ABD00059299-D?

It's frame R11, which is a module-style cabinet-mount drive in the ACS880-04 family.

What are the normal-use and heavy-duty ratings?

Normal use: 560 kW output power at 590 A. Heavy-duty use: 500 kW at 505 A. Light-overload use: 560 kW at 571 A.

MPN
3ABD00059299-D