Skip to main content
ABB 3ABD00059582-D — AC Drive (VFD) 600V

ABB 3ABD00059582-D ACS880-01 Drive, 30 kW, 35 A, 525-690 V

MPN3ABD00059582-D
Active

ABB ACS880-01, 30 kW, 35 A, 525-690 VAC, 3-phase, IP21, wall-mounted, IE2, frame size R5.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3ABD00059582-D — Identification
ParameterValue
Frame sizeR5

Electrical (input)

3ABD00059582-D — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz

Output / Performance

3ABD00059582-D — Output / Performance
ParameterValue
Output power, normal duty30 kW
Output power, heavy duty22 kW
Output power, light overload30 kW
Output current, normal duty35 A
Output current, heavy duty26 A
Output current, light overload33 A
Efficiency level (IE class)IE2

Mechanical

3ABD00059582-D — Mechanical
ParameterValue
Mounting typeWall-mounted
NEMA enclosure typeType1

Environmental

3ABD00059582-D — Environmental
ParameterValue
Degree of protection (IEC, IP)IP21

Product details

The ABB ACS880-01 order code 3ABD00059582-D is a wall-mounted single drive rated for 30 kW normal-duty output at 35 A, with a heavy-duty rating of 22 kW at 26 A and a light-overload rating of 30 kW at 33 A. Input voltage range is 525 to 690 VAC three-phase, 47.5 to 63 Hz. The IP21 enclosure and NEMA Type 1 rating suit clean indoor panel or machine-mount installations where washdown protection isn't required.

Duty ratings & what they mean

The normal-use rating (30 kW, 35 A) covers constant-torque loads like conveyors and positive-displacement pumps at full rated current. IE2 efficiency level means the drive meets the EU efficiency class for motor-driven systems.

Wall-mounted frame size R5. The IP21 enclosure allows indoor installation in electrical rooms or on machine frames where no liquid ingress is expected. NEMA Type 1 provides basic protection against incidental contact. The 525-690 V input range covers 600 V and 690 V industrial networks common in mining, oil & gas, and heavy manufacturing.

Frequently asked questions

Where can I buy 3ABD00059582-D and how do I get a price?

This drive is sourced to order against an RFQ through independent distribution. Submit a quote request for current pricing and availability confirmation.

What is 3ABD00059582-D's frame size?

The drive is built on frame size R5, which is the physical footprint for the 30 kW class in the ACS880-01 wall-mount family.

What input voltage and frequency does this drive accept?

Input voltage range is 525 to 690 VAC three-phase, 47.5 to 63 Hz. This covers 50 Hz and 60 Hz industrial mains at 600 V and 690 V nominal.

What is the difference between the normal-duty and heavy-duty ratings?

Normal duty is 30 kW at 35 A for constant-torque loads. Heavy duty is 22 kW at 26 A for variable-torque or high-overload applications. Use the heavy-duty figure when sizing the drive to a motor that may see sustained overload conditions.

MPN
3ABD00059582-D