The 3ADT218587S0213: Rated 0900 A on a 600 VAC supply at 50 Hz. That's the continuous output current into a DC motor armature; the 4Q topology means it regenerates — useful for unwind stands, hoists, or any axis that back-drives. The 73 dB(A) sound level is loud enough to notice in a quiet control room but normal for an H6-frame converter at full load. Three analog inputs and two analog outputs are onboard; enough for speed reference and tacho feedback plus one spare channel for torque or current monitoring. Protection is IP00 on the auxiliary terminals per IEC 60529, IEC 60947-1, and EN 60529 — no enclosure, so it's intended for installation inside a cabinet that provides the final IP rating. Operating humidity spans 5 to 95 % RH, non-condensing.
Frame H6 means the mounting centers and bus-bar positions are fixed. The DCS880 family shares a common DC bus architecture if you're paralleling units for higher current. Analog inputs are configurable for voltage or current; the two analog outputs can be scaled to track armature current or speed. Verify your existing line reactor and DC choke ratings against the 0900 A continuous draw before commissioning.