Skip to main content
ABB 3AUD0000000068 — AC Drive (VFD) 480V

ABB 3AUD0000000068 HVAC Drive, 150 Hp, 180 A, UL Type3R

MPN3AUD0000000068
Active

ABB ACH580 series HVAC drive, order code 3AUD0000000068, UL rated 150 Hp / 180 A light-overload, 380-480 V 3-phase, NEMA Type3R enclosure with integrated circuit breaker disconnect.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000000068 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000000068 — Power & Output
ParameterValue
Output current, light overload (UL rating)180 A
Output power, light overload (UL rating, Hp)150 Hp
3AUD0000000068 — Mechanical & Cooling
ParameterValue
NEMA enclosure typeType3R

Product details

Drive selection memo — HVAC duty, UL footprint

The ABB 3AUD0000000068 is an ACH580-series HVAC drive with a built-in circuit breaker disconnect, UL listed for 150 Hp light-overload use at 180 A output current. That 180 A figure governs the motor full-load amps it can sustain — match it to the nameplate FLA of the fan or pump, not the motor frame size. Input voltage range is 380 to 480 V three-phase, 50/60 Hz, which covers standard North American 460 V and European 400 V distribution without a transformer. The NEMA Type3R enclosure means it's rated for outdoor installation — rain-tight, sleet-resistant, but not submersible. Plan for a drip shield if direct overhead exposure is likely.

This is a current-production catalog item, not a phase-out or last-time-buy.

Integration notes — panel and field wiring

The integrated circuit breaker disconnect eliminates the need for a separate branch-circuit protective device upstream, saving a panel space column. Type3R rating allows direct wall-mount outdoors without a secondary enclosure, but the gland plate entry must use rain-tight conduit hubs to maintain the seal. Verify the disconnect handle protrusion clears any adjacent equipment swing radius.

Frequently asked questions

What is the UL output rating for this drive?

UL listed for 150 Hp light-overload use with 180 A output current. That 180 A is the continuous current rating under UL light-overload conditions — match it to the motor FLA, not the frame size.

What enclosure type does this drive have?

NEMA Type3R enclosure, rated for outdoor use — rain-tight and sleet-resistant. Not submersible; use rain-tight conduit hubs at the gland plate to maintain the seal.

MPN
3AUD0000000068