ABB 3AUD0000000086 — AC Drive (VFD) 480V

ABB 3AUD0000000086 HVAC Drive, 250 Hp, 302 A, 380-480 V

MPN3AUD0000000086
Active

ABB, ACH580-PDR series, HVAC drive with disconnect, UL rated 250 Hp / 302 A light-overload, 380-480 V 3-phase, NEMA 3R, 50/60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000000086 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000000086 — Power & Output
ParameterValue
Output current, light overload (UL rating)302 A
Output power, light overload (UL rating, Hp)250 Hp
3AUD0000000086 — Mechanical & Cooling
ParameterValue
NEMA enclosure typeType3R

Product details

HVAC drive with integrated disconnect

The ABB 3AUD0000000086 is an HVAC drive with a built-in disconnect switch, part of the ACH580-PDR series. It is UL rated for light-overload use at 250 Hp with a corresponding output current of 302 A, making it suitable for driving large fan, pump, and compressor loads in commercial and industrial HVAC systems. The drive accepts a 3-phase input voltage of 380 to 480 V and operates at 50/60 Hz, covering the standard global mains frequencies. The NEMA 3R enclosure means it is rated for outdoor installation — rain-tight and sleet-resistant — so it can be mounted on a roof or exterior wall without a separate weather shelter.

The 302 A output current at light-overload (UL) is the figure that governs motor sizing: it tells you the drive can deliver full rated current continuously for a variable-torque load like a centrifugal fan or pump. The 250 Hp rating is the corresponding motor horsepower at 480 V. If your load is constant-torque (conveyor, positive-displacement pump), you would need to consult the heavy-overload current rating — not listed here — which is typically lower. The NEMA 3R enclosure eliminates the need for a separate disconnect and enclosure on outdoor installations. The integrated disconnect saves panel space and wiring labor, but verify that the disconnect's interrupting rating coordinates with your upstream overcurrent protection.

Frequently asked questions

What is the input voltage and frequency for 3AUD0000000086?

The drive accepts a 3-phase input of 380 to 480 V at 50/60 Hz.

What enclosure type does this drive have?

It has a NEMA 3R enclosure, rated for outdoor use — rain-tight and sleet-resistant.

Where can I buy 3AUD0000000086 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

MPN
3AUD0000000086