3AUD0000000100 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000000100 — Electrical Output
ParameterValue
Output power, light-overload duty (UL, Hp)75 Hp
Output current, light-overload duty (UL)211 A
3AUD0000000100 — Mechanical
ParameterValue
Enclosure type (NEMA)Type3R

Product details

The 3AUD0000000100 is an ABB HVAC packaged drive — a variable-frequency drive, circuit breaker disconnect, and e-clipse bypass all in one NEMA Type3R enclosure. Rated for 75 Hp light-overload duty at 211 A per UL, on a 208-240 V three-phase supply. The 50/60 Hz line frequency is handled natively; no transformer tap change needed for 50 Hz sites.

The 211 A light-overload current (UL) is the continuous rating that governs conductor sizing and upstream breaker coordination — not the motor nameplate alone. The 75 Hp figure assumes a standard 4-pole induction motor at 240 V; derate proportionally if running at 208 V. NEMA Type3R means the enclosure is rainproof and sleet-resistant for outdoor rooftop or pad-mounted installation, but it is not submersible or dust-tight.

Deployment context

The NEMA Type3R enclosure suits outdoor HVAC installations — chillers, cooling towers, rooftop air handlers — where the drive must tolerate rain, snow, and ice without an additional weather shelter. The integrated e-clipse bypass allows the motor to run across-the-line if the VFD section is taken offline for service, keeping the fan or pump moving.

Frequently asked questions

What is 3AUD0000000100's listed frequency rating?

The drive accepts 50/60 Hz line frequency — no hardware change needed between 50 Hz and 60 Hz grids.

Where can I buy 3AUD0000000100 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price figure is published here.

What enclosure type does 3AUD0000000100 carry?

NEMA Type3R — rainproof and sleet-resistant, suitable for outdoor installation without additional weather protection.

MPN