The ABB 3AUD0000000695 is an HVAC packaged ultra-low harmonic drive with a non-fused disconnect switch integrated. It is rated for 15 Hp light-overload use at 460 V, delivering 23 A output current (UL). The 3-phase input accepts 440–480 V at 50/60 Hz. Frame size is R3. The IP21 and NEMA Type 1 enclosure means this drive is suited for indoor installation in a clean environment — no washdown protection, but fine for a mechanical room or rooftop unit with a shelter. The non-fused disconnect provides a local lockout point, which simplifies compliance with NFPA 70E for maintenance isolation.
The 23 A light-overload rating (UL) governs the motor full-load current it can carry continuously. For a 15 Hp, 460 V motor drawing roughly 21 A FLA, this drive provides about 10% headroom — adequate for most fan and pump loads. The ultra-low harmonic design (typically <5% THDi) means it meets IEEE 519 without a separate filter, which saves panel space and avoids the insertion loss of a line reactor.