ABB 3AUD0000000695 — AC Drive (VFD) 480V

ABB 3AUD0000000695 ACH580 HVAC Drive, 15 Hp, 23 A, 460 V

MPN3AUD0000000695
Active

ABB ACH580 HVAC packaged ultra-low harmonic drive, 3AUD0000000695, R3 frame, 15 Hp, 23 A, 460 V, 3-phase, IP21, NEMA 1, 50/60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000000695 — Input / Supply
ParameterValue
Input voltage range440 ... 480 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000000695 — Power & Output
ParameterValue
Output current, light overload (UL rating)23 A
Output power, light overload (UL rating, Hp)15 Hp
3AUD0000000695 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeType1
Degree of protection (IP)IP21

Product details

The ABB 3AUD0000000695 is an HVAC packaged ultra-low harmonic drive with a non-fused disconnect switch integrated. It is rated for 15 Hp light-overload use at 460 V, delivering 23 A output current (UL). The 3-phase input accepts 440–480 V at 50/60 Hz. Frame size is R3. The IP21 and NEMA Type 1 enclosure means this drive is suited for indoor installation in a clean environment — no washdown protection, but fine for a mechanical room or rooftop unit with a shelter. The non-fused disconnect provides a local lockout point, which simplifies compliance with NFPA 70E for maintenance isolation.

The 23 A light-overload rating (UL) governs the motor full-load current it can carry continuously. For a 15 Hp, 460 V motor drawing roughly 21 A FLA, this drive provides about 10% headroom — adequate for most fan and pump loads. The ultra-low harmonic design (typically <5% THDi) means it meets IEEE 519 without a separate filter, which saves panel space and avoids the insertion loss of a line reactor.

Frequently asked questions

What is the frame size of 3AUD0000000695?

The frame size is R3. This determines the mounting footprint and conduit entry locations for panel integration.

What is the input voltage and frequency for this drive?

Input voltage is 440–480 V, 3-phase, 50/60 Hz.

What compliance documentation is available for 3AUD0000000695?

The drive carries UL listing and is designed for the North American market. Standard ABB documentation includes the ACH580 hardware manual and quick start guide. For specific RoHS/REACH declarations, consult the ABB product compliance portal or request them with your RFQ.

MPN
3AUD0000000695