Skip to main content
ABB 3AUD0000003509 — AC Drive (VFD) 480V

ABB 3AUD0000003509 ACQ580 Irrigation Drive, 50 Hp, 143 A, 20

MPN3AUD0000003509
Active

ABB ACQ580 irrigation drive package, 3AUD0000003509, UL: Pld 50 Hp, 143 A, 460 V, Frame R6, NEMA Type 1, IP21, 3-phase, 208-240 V input, 50/60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000003509 — Input / Supply
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000003509 — Power & Output
ParameterValue
Output current, light overload (UL rating)143 A
Output power, light overload (UL rating, Hp)50 Hp
3AUD0000003509 — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType1
Degree of protection (IP)IP21
3AUD0000003509 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)40 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)114 A

Product details

The ABB 3AUD0000003509 is an ACQ580-series irrigation drive package built for 3-phase pump loads on 208-240 VAC mains. It carries dual UL output ratings: 40 Hp / 114 A for heavy-duty use and 50 Hp / 143 A for light-overload duty at 460 V — the light-overload figure governs continuous pump operation, while the heavy-duty rating applies when the drive must handle sustained overload profiles typical of well pumps with high starting torque. Frame size R6 and NEMA Type 1 enclosure (IP21) mean it is intended for indoor panel or protected outdoor installation — not direct washdown exposure.

The 114 A heavy-duty rating (40 Hp) applies when the drive must sustain 150% overload for 60 seconds, typical for starting high-inertia loads or for applications with repeated surge cycles. Use the heavy-duty number for sizing branch-circuit protection and conductors. Input voltage range is 208-240 V three-phase. On a 208 V supply the output current capability derates proportionally; verify the motor's FLA against the drive's output current at the actual line voltage before committing the BOM line.

Frequently asked questions

What is the frame size of 3AUD0000003509?

The frame size is R6, which determines the mounting footprint, conduit entry locations, and heat sink dimensions for panel layout.

What is the input voltage and frequency range?

Input voltage is 208-240 V three-phase at 50/60 Hz. The drive accepts both 50 Hz and 60 Hz supplies without modification.

What are the UL output ratings for this drive?

UL heavy-duty rating is 40 Hp / 114 A; light-overload rating is 50 Hp / 143 A, both at 460 V. The light-overload figure governs continuous pump duty.

Where can I buy 3AUD0000003509 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not estimated.

MPN