The ABB 3AXD50000031875 is a variable-frequency drive sized for a 1.1 kW motor on single-phase 200–240 V input. Normal-use output current is 6.9 A; heavy-duty use drops to 0.75 kW and 4.8 A.
Input is single-phase 200–240 V, 47.5–63 Hz. Power factor is 0.98; standby loss is 15 W. It carries 2 analog inputs and 1 analog output, plus 5 digital I/O and 2 digital outputs. The control unit is included, so no separate order for the logic board.