Skip to main content
ABB 3AXD50000031878 — AC Drive (VFD) 240V

ABB 3AXD50000031878 ACS580 drive, 3 kW normal duty, 1-phase

MPN3AXD50000031878
Active

ABB ACS580, general purpose VFD, 3AXD50000031878, 3 kW normal duty / 2.2 kW heavy duty, 1-phase 200-240 V input, IP20, R2 frame, MODBUS.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000031878 — Electrical Output
ParameterValue
Output power, normal duty (Pn)3 kW
Output current, normal duty (In)12.2 A
Output power, heavy duty (PhD)2.2 kW
Output current, heavy duty (IhD)9.8 A
Output power, light-overload duty (PlD)3.0 kW
Output current, light-overload duty (IlD)11.6 A
Output power, heavy duty (UL, Hp)3 Hp
Output current, heavy duty (UL)9.3 A
Apparent power output4.9 kV·A
Output power, light-overload duty (UL, Hp)3 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)11.6 A
Standby loss15 W
Power consumption115 W
3AXD50000031878 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases1-phase
Frequency47.5 ... 63 Hz
Power factor0.98
3AXD50000031878 — Control & I/O
ParameterValue
Digital inputs / outputs5 / 2
Communication protocolMODBUS
Analog inputs2
Analog outputs1
Hardware interfacesIndustrial Ethernet 0
3AXD50000031878 — Environmental
ParameterValue
Operating humidity5 ... 95
Altitude1000 m
Noise level58.80 dB(A)
3AXD50000031878 — Mechanical
ParameterValue
Degree of protection (IP)IP20
Enclosure type (NEMA)Open Type
Frame sizeR2
Mounting typeModule
3AXD50000031878 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

Drive ratings and load profiles

The 3AXD50000031878: Input is single-phase 200-240 V, 47.5-63 Hz. Because it's a single-phase feed, the drive is exempt from EU ecodesign efficiency reporting under Regulation 2019/1781 — the IE2 efficiency class listed applies to the three-phase input variants of this platform, not this one. Frame size R2, IP20 open-type enclosure. Mounts as a module. The apparent power output is 4.9 kVA, standby loss 15 W, and full-load power consumption 115 W. Sound level is 58.8 dB(A).

Altitude rating 1000 m without derating. Operating humidity 5-95% RH (non-condensing). UL listing is present: heavy-duty output 3 Hp at 9.3 A, light-overload output 3 Hp at 11.6 A.

Frequently asked questions

What is the SCIP number for this drive?

SCIP number 577e5c08-5a76-40f0-9d37-146997f79a79, registered in Finland.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20230303). REACH declaration confirms substances >0.1 mass percentage (date 20250905). UL listing covers heavy-duty and light-overload output ratings.

What are the key output ratings?

Normal use: 3 kW at 12.2 A. Heavy duty: 2.2 kW at 9.8 A. Light overload: 3.0 kW at 11.6 A. Input is single-phase 200-240 V.

MPN
3AXD50000031878