ABB 3AXD50000031895 — AC Drive (VFD) 480V

ABB 3AXD50000031895 ACS580 drive, R3 frame, 11 kW, 25 A

MPN3AXD50000031895
Active

ABB ACS580 general purpose drive, 3AXD50000031895, R3 frame, 11 kW / 25 A normal use, 7.5 kW / 17 A heavy duty, 3-phase 380-480 V, IP20, MODBUS.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000031895 — Power & Output
ParameterValue
Output power, normal duty11 kW
Output current, normal duty25.0 A
Output power, heavy duty7.5 kW
Output current, heavy duty17.0 A
Output power, light overload11.0 kW
Output current, light overload23.8 A
Output current, light overload (UL rating)21 A
Apparent power output17 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)15 Hp
Standby power loss26 W
3AXD50000031895 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000031895 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000031895 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C
3AXD50000031895 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)10 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)14 A

Product details

The 3AXD50000031895: The 5 digital inputs and 2 digital outputs, plus 2 analog inputs and 1 analog output, cover basic I/O for a standalone pump or fan application without an expansion module. Standby loss sits at 26 W, and the maximum ambient is 50 °C — derate above that if the panel runs hot. The R3 frame is a common size for this power band; mounting is module-style on a backplate or DIN-rail adapter (not included).

Heavy-duty vs normal-use ratings

The drive carries three distinct output ratings: normal use (11 kW / 25 A), light-overload use (11 kW / 23.8 A), and heavy-duty use (7.5 kW / 17 A). Under UL listing, the normal-use current drops to 21 A, and heavy-duty output is 10 Hp / 14 A. The light-overload column (23.8 A) is for variable-torque fans and centrifugal pumps where peak demand stays brief.

Rated for installation up to 1000 m altitude without derating. Operating humidity range is 5-95% RH (non-condensing). Sound pressure level is 65.8 dB(A) — noticeable in a quiet control room but typical for an R3 drive at full load. The WEEE category is 5 (small equipment under 50 cm), so end-of-life disposal routing is straightforward. Mount the module on a flat backplate with clearance for airflow; IP20 means no protection against water ingress, so keep it inside the panel.

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 11 kW / 25 A. Heavy-duty use: 7.5 kW / 17 A. Light-overload use: 11 kW / 23.8 A. UL normal use: 21 A; UL heavy-duty: 10 Hp / 14 A.

What communication protocol does it support?

MODBUS is the onboard protocol. No Industrial Ethernet interface is included on this variant.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 2023-03-03). REACH declaration confirms substances above 0.1% (date 2025-09-05). SCIP number df291eaa-8422-40ff-acd0-55c77c3d1d9f (Finland). UL listing with separate current and horsepower ratings for normal and heavy-duty use.

What is the frame size and mounting type?

Frame size R3. Mounting type is module — typically backplate-mounted; IP20 open-type enclosure.