It is rated for 3-phase 200-240 V input at 47.5-63 Hz, delivering 3 kW / 14 A in normal use (light-overload also 3 kW / 13 A) and 2.2 kW / 11 A in heavy-duty use. UL ratings mirror these at 3 Hp / 13 A light-overload and 3 Hp / 11 A heavy-duty. The module includes a PC connection for commissioning, has 6 digital inputs and 5 digital outputs, plus 2 analog inputs and 2 analog outputs. Communication is via CAN. The enclosure is IP20, Open Type, rated for maximum 40 °C ambient, 5-95% humidity, and 1000 m altitude.
Duty Cycle and Sizing
Normal use: 14 A; light-overload: 13 A; heavy-duty: 11 A. The heavy-duty rating is the binding constraint for constant-torque loads.
Frame size R2, module mounting. The IP20 rating suits cabinet installation; the Open Type enclosure means it requires a separate enclosure for environmental protection. Standby loss is 30 W, sound level 39 dB(A). The apparent power output is 5.6 kV·A, power factor 0.98. The module includes a lithium coin cell (CR2032, 220 mAh, 3 V, two pieces).