The 3AXD50000036397: Normal-use output (Pn 15 kW, In 61 A) is the continuous rating for a typical constant-torque fan or pump load. Heavy-duty use (PhD 11 kW, IhD 52 A) is the rating for higher starting torque or cyclic overloads — a conveyor or extruder drive, for example. Light-overload use (PlD 15 kW, IlD 57 A) sits between the two. On UL listings the same heavy-duty current (52 A) is rated 15 Hp, and the light-overload current (57 A) is rated 20 Hp. Pick the duty class that matches your application's actual load profile, not just the motor nameplate.
Integration notes
Mounts as a module (R4 frame). Includes a PC connection port. Communication is CAN protocol — no onboard Industrial Ethernet interface. Digital I/O: 6 inputs, 5 outputs. Analog I/O: 2 inputs, 2 outputs. Operating humidity 5–95% RH, max ambient temperature 40 °C. Standby loss 31 W. Sound level 70 dB(A). Power factor 0.98. Frequency range 47.5–63 Hz. Battery: two CR2032 lithium coin cells (220 mAh, 3 V).