The 3AXD50000046387: Input frequency range is 47.5–63 Hz, so it handles weak grids or generator supply without derating. Maximum ambient temperature is 40 °C; operating humidity spans 5–95% non-condensing. Altitude rating goes to 4000 m — useful for high-altitude installations without forced derating. The drive includes a control unit, so you're not buying a power section alone — it's ready to commission out of the box. Communication is via CAN; there are no industrial Ethernet ports on this variant, so plan for a gateway if you need PROFINET or EtherNet/IP.
Wall-mounted, IP21 enclosure with NEMA Type 1 rating. That means it's suitable for indoor use where dripping water or light splashes aren't expected. The R3 frame is compact enough for panel or machine-mount applications. Sound level is 60 dB(A) — noticeable but not loud enough to require an enclosure for noise control in most industrial settings. Standby loss is 25 W; full-load power consumption is 271 W. Factor that into your panel cooling budget if the drive is in a sealed cabinet.
I/O and control
Efficiency is rated IE2 — standard for this class. The drive includes two CR2032 lithium coin cells (220 mAh each) for real-time clock backup and parameter retention.
UL ratings are provided for the North American market: heavy-duty use at 10 Hp (14.3 A), light-overload at 15 Hp (18 A). No normal-use UL current is listed, so for UL-listed installations, size based on the heavy-duty or light-overload curves. WEEE category is 5 (small equipment).