ABB 3AXD50000049065 — AC Drive (VFD) 480V

ABB 3AXD50000049065 Drive Module, R10, 315 kW, 585 A

MPN3AXD50000049065
Active

ABB, drive module, 3AXD50000049065, R10 frame, 315 kW normal use / 585 A, 250 kW heavy duty / 429 A, BACnet, IP00, IE2.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000049065 — Power & Output
ParameterValue
Output power, normal duty315 kW
Output current, normal duty585 A
Output power, heavy duty250 kW
Output current, heavy duty429 A
Output power, light overload315 kW
Output current, light overload575 A
Output current, light overload (UL rating)573 A
Apparent power output405 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)450 Hp
Standby power loss423 W

Input / Supply

3AXD50000049065 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3AXD50000049065 — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeModule

Environmental

3AXD50000049065 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Electrical

3AXD50000049065 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)350 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)414 A

Product details

Drive module for 380–480 V three-phase systems

The ABB 3AXD50000049065 is a drive module on an R10 frame, rated for 315 kW normal use (585 A output) and 250 kW heavy-duty use (429 A output) from a 380–480 V three-phase supply. It includes the control unit and communicates via BACnet.

This module carries three duty ratings that map to different application profiles. Heavy-duty use (PhD 250 kW, IhD 429 A) applies to constant-torque or high-starting-torque applications such as conveyors or extruders. Light-overload use (PlD 315 kW, IlD 575 A) covers intermittent overloads above the normal rating. The UL listing confirms the same currents: 585 A normal, 414 A heavy duty (350 Hp), and 573 A light overload (450 Hp).

Integration notes

Mounts as a module; the R10 frame determines the physical footprint and bus bar connections. Ambient temperature must not exceed 40 °C, and installation altitude is limited to 1000 m without derating. Standby loss is 423 W, and full-load power consumption is 6840 W. The control unit includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. There is no onboard industrial Ethernet interface — BACnet is the communication protocol. A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock. Sound level is 72 dB(A).

Frequently asked questions

What are the key ratings for this drive module?

Normal use: 315 kW, 585 A. Heavy-duty use: 250 kW, 429 A. Light-overload use: 315 kW, 575 A. Input is 380–480 V three-phase.

What compliance documentation is available?

RoHS per EU Directive 2011/65/EU and Amendment 2015/863, REACH declaration (substances > 0.1% present), and UL listing for normal/heavy-duty/light-overload currents and horsepower.

What communication protocol does this module use?

BACnet. There is no onboard industrial Ethernet interface.

MPN
3AXD50000049065