Duty ratings and motor sizing
The 3AXD50000050412: Normal-use (Pn) is 160 kW at 174 A; heavy-duty (PhD) is 132 kW at 142 A; light-overload (PlD) is 160 kW at 165 A. The heavy-duty figure governs continuous motor load in high-torque applications — size the motor to the 142 A limit if the load profile includes sustained overload. UL heavy-duty rating is 150 Hp at 144 A.
Input and environmental limits
Input voltage range is 525–690 V AC, 48–63 Hz, 3-phase. Maximum ambient temperature 40 °C, altitude 1000 m without derating. Operating humidity 5–95 % RH. Sound level 77 dB(A).
Two analog inputs, two analog outputs. Seven digital inputs and five digital outputs. Communication via CAN; no onboard Industrial Ethernet. Control unit included.
SCIP number 82D82DAE-9725-4373-865D-AA949B97DE50 Finland. WEEE Category 4 (Large Equipment). This regenerative drive is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).