Skip to main content
ABB 3AXD50000115266 — AC Drive (VFD) 600V

ABB 3AXD50000115266 R11 Regenerative Drive, 160 kW

MPN3AXD50000115266
Active

ABB, regenerative drive, frame size R11, 3AXD50000115266, 160 kW normal duty, 525–690 V input, 174 A output, IP20, Open Type.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000115266 — Identification
ParameterValue
Frame sizeR11
3AXD50000115266 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3AXD50000115266 — Output / Performance
ParameterValue
Output power, normal duty160 kW
Output power, heavy duty132 kW
Output power, light overload160 kW
Output current, normal duty174 A
Output current, heavy duty142 A
Output current, light overload165 A
Efficiency level (IE class)IE2
Output power (UL), light overload175 Hp
Output power (UL), heavy duty150 Hp
Output current (UL), light overload168 A
Output current (UL), heavy duty144 A
3AXD50000115266 — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3AXD50000115266 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The ABB 3AXD50000115266 is a regenerative AC drive in frame size R11, built for three-phase 525–690 V supplies at 47.5–63 Hz. It delivers 160 kW in normal-duty (light-overload) use and 132 kW in heavy-duty use, with corresponding output currents of 174 A and 142 A. The regenerative design means it can feed braking energy back into the line — exempt from EU ecodesign efficiency rules (Regulation EU/2019/1781, §2.3.c) because the energy recovery itself improves system efficiency.

IP20 Open Type means it's for indoor cabinet mounting, not washdown or dust-heavy areas. The 4000 m altitude rating covers high-altitude installations without derating, which matters for mines or mountain-site processing. Standby loss of 214 W and sound level of 75 dB(A) are figures to budget for in panel cooling and noise surveys.

Frequently asked questions

What compliance documentation does ABB provide for this drive?

RoHS compliance per EU Directive 2011/65/EU (date 20240508), REACH declaration with substances >0.1% (date 20250905), UL listing for heavy-duty 150 Hp / 144 A and light-overload 175 Hp, and SCIP number 7f3c52d9-0321-456d-a5b5-7fcf00de29a4 Finland.

What is the altitude rating of 3AXD50000115266?

It is rated for installation at altitudes up to 4000 m without derating.

MPN