Output ratings and duty selection
The 3AXD50000115273: Three duty ratings are listed: normal-use (Pn 200 kW, In 210 A), heavy-duty (PhD 160 kW, IhD 174 A), and light-overload (PlD 200 kW, IlD 200 A). The heavy-duty figure governs continuous motor load in constant-torque applications; the normal-use figure applies to variable-torque loads such as pumps and fans. UL listings show 175 Hp heavy-duty and 200 Hp light-overload.
Rated for a maximum ambient temperature of +55 °C, altitude up to 4000 m, and operating humidity 5–95% RH. Enclosure is Open Type with IP20 protection — suitable for clean, dry indoor panels. Sound level is 75 dB(A). The module includes a control unit; frame size R11.
Provides 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is via CAN; no industrial Ethernet interface is present. A lithium coin cell (CR2032, 220 mAh, 3 V, 2 pcs) backs the real-time clock.