Skip to main content
ABB 3AXD50000115303 — AC Drive (VFD) 600V

ABB 3AXD50000115303 R11 Regenerative Drive, 355 kW, 370 A

MPN3AXD50000115303
Active

ABB regenerative drive unit, frame size R11, 355 kW normal-use output, 370 A, 525–690 V 3-phase input, IP20, includes control unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000115303 — Identification
ParameterValue
Frame sizeR11
3AXD50000115303 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3AXD50000115303 — Output / Performance
ParameterValue
Output power, normal duty355 kW
Output power, heavy duty315 kW
Output power, light overload355 kW
Output current, normal duty370 A
Output current, heavy duty330 A
Output current, light overload360 A
Efficiency level (IE class)IE2
Output power (UL), light overload350 Hp
Output power (UL), heavy duty300 Hp
Output current (UL), light overload336 A
Output current (UL), heavy duty289 A
3AXD50000115303 — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3AXD50000115303 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The ABB 3AXD50000115303 is a regenerative drive unit in frame size R11, delivering 355 kW output power at 370 A under normal use, with a 525 to 690 V three-phase input. It includes the control unit and is rated IP20, open-type enclosure. The drive is exempt from EU ecodesign efficiency reporting per Regulation EU/2019/1781 §2.3.c, as regenerative units are not required to provide energy-efficiency data.

Normal-use output is 355 kW at 370 A; heavy-duty use is 315 kW at 330 A; light-overload use is 355 kW at 360 A. UL heavy-duty is 300 Hp at 289 A; UL light-overload is 350 Hp.

Environmental and installation limits

Ambient temperature maximum is +55 °C. Altitude rating is 4000 m. Operating humidity range is 5 to 95 %.

Two analog inputs and two analog outputs are provided. Digital I/O counts six inputs and two outputs. Communication is via CAN protocol; no industrial Ethernet interface is fitted (0 hardware interfaces for Ethernet). The drive includes a lithium coin cell (CR2032, 220 mAh, 3 V, two pieces) for real-time clock backup.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 355 kW at 370 A; heavy-duty use is 315 kW at 330 A; light-overload use is 355 kW at 360 A. UL heavy-duty is 300 Hp at 289 A; UL light-overload is 350 Hp.

What compliance documentation is available for this part?

RoHS compliance per EU Directive 2011/65/EU (date 20240508), REACH declaration (date 20250905), SCIP number 7f3c52d9-0321-456d-a5b5-7fcf00de29a4 Finland, and UL listing for heavy-duty and light-overload ratings.

What is the input voltage and frequency range?

Input voltage is 525 to 690 V three-phase, frequency range 47.5 to 63 Hz.

What is the altitude and temperature rating?

Maximum ambient temperature is +55 °C; altitude rating is 4000 m.

MPN
3AXD50000115303