ABB 3AXD50000137145 — AC Drive (VFD) 240V

ABB 3AXD50000137145 drive control unit, R4, 15 kW, 55 A

MPN3AXD50000137145
Active

ABB 3AXD50000137145 drive control unit, frame size R4, 15 kW / 55 A normal-use output, 200-240 V 3-phase input, IP20, CAN interface.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000137145 — Electrical Output
ParameterValue
Output power, normal duty (Pn)15 kW
Output current, normal duty (In)55.0 A
Output power, heavy duty (PhD)11.0 kW
Output current, heavy duty (IhD)48.0 A
Output power, light-overload duty (PlD)15.0 kW
Output current, light-overload duty (IlD)52.8 A
Output power, heavy duty (UL, Hp)15 Hp
Output current, heavy duty (UL)46.2 A
Apparent power output22 kV·A
Output power, light-overload duty (UL, Hp)15 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)52.8 A
Standby loss35 W
Power consumption676 W

Electrical Input

3AXD50000137145 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98

Control & I/O

3AXD50000137145 — Control & I/O
ParameterValue
Digital inputs / outputs2 / 1
Communication protocolCAN
Analog inputs0
Analog outputs0
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000137145 — Environmental
ParameterValue
Temperature rating, max.Maximum 50 °C
Operating humidity5 ... 95
Altitude1000 m
Noise level69.00 dB(A)

Mechanical

3AXD50000137145 — Mechanical
ParameterValue
Degree of protection (IP)IP20
Enclosure type (NEMA)Open Type
Frame sizeR4
Mounting typeModule

Approvals

3AXD50000137145 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000137145 is a drive control unit in frame size R4, rated for 15 kW normal-use output at 55.0 A and 11.0 kW heavy-duty use at 48.0 A on a 200-240 V three-phase supply (47.5-63 Hz). It includes the control unit, communicates via CAN, and carries IP20 protection for panel-mount installations.

Normal-use output current (In) is 55.0 A; heavy-duty (Ihd) is 48.0 A. Light-overload use (Ild) is 52.8 A. The apparent power output is 22 kV·A. Efficiency is rated IE2. For UL-listed installations, heavy-duty output is 15 Hp at 46.2 A, light-overload is 15 Hp at 52.8 A. Ambient temperature maximum is 50 °C; altitude rating is 1000 m. Operating humidity range is 5-95% RH. Standby loss is 35 W; power consumption at rated load is 676 W. Sound level is 69 dB(A).

I/O and interfaces

The unit provides 2 digital inputs and 1 digital output. It has no analog inputs or outputs, and no industrial Ethernet interface. Communication is via CAN.

Frequently asked questions

What compliance documentation does this part have?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, REACH registered (contains substances > 0.1 mass percentage), SCIP number d2b14b17-a814-48a9-a8d0-6446beb58737 Finland, and UL ratings for heavy-duty and light-overload use are provided.

MPN