Skip to main content
ABB 3AXD50000145959 — AC Drive (VFD) 600V

3AXD50000145959 ABB ACS880-17-1680A-7 Drive, 1600 kW, 1680 A

MPN3AXD50000145959
Active

ABB ACS880-17 series regenerative drive, 3AXD50000145959, 1600 kW normal use, 1680 A output, 525-690 V input, IP22, NEMA 1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145959 — Identification
ParameterValue
Frame size3xR8i+3xR8i
3AXD50000145959 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range48 ... 63 Hz
3AXD50000145959 — Output / Performance
ParameterValue
Output power, normal duty1600 kW
Output power, heavy duty1200 kW
Output power, light overload1500 kW
Output current, normal duty1680 A
Output current, heavy duty1257 A
Output current, light overload1613 A
Output power (UL), light overload1750 Hp
Output power (UL), heavy duty1250 Hp
Output current (UL), light overload1613 A
Output current (UL), heavy duty1257 A
3AXD50000145959 — Mechanical
ParameterValue
NEMA enclosure typeType1
3AXD50000145959 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP22

Product details

The 3AXD50000145959: Ambient limit is 40 °C, altitude 1000 m without derating. Sound level is 78 dB(A) — plan for ear protection if the drive is in a walk-in area. The control unit is included; 14 digital I/O and 4 analog inputs plus 4 analog outputs are on board. Communication is CAN; there is no Industrial Ethernet port on this variant.

SCIP number 944D8A5E-036D-404E-9036-0D3C1EA703AD (Finland) is on file for EU waste reporting. WEEE category 4 (Large Equipment). The regenerative drive is exempt from EU ecodesign energy-efficiency requirements under Regulation EU/2019/1781 §2.3.c — no efficiency class is provided. The drive contains two BR2032 lithium coin cells (3 V, 200 mAh each).

Frequently asked questions

What are the key ratings of this drive?

Normal-use output is 1600 kW / 1680 A at 525-690 V input. Heavy-duty use is 1200 kW / 1257 A; light-overload use is 1500 kW / 1613 A. Apparent power output is 2008 kV·A.

What is the SCIP number for this drive?

SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD, registered in Finland.

What is the altitude rating?

Rated for 1000 m without derating.

What compliance documentation is available?

SCIP number on file, WEEE category 4, and ecodesign exemption for regenerative drives. The drive includes two BR2032 lithium coin cells.

MPN
3AXD50000145959