Skip to main content
ABB 3AXD50000145973 — AC Drive (VFD) 600V

ABB 3AXD50000145973 ACS880-17 Drive, 2200 kW, 2230 A

MPN3AXD50000145973
Active

ABB ACS880-17 regenerative drive, 3AXD50000145973, 2200 kW / 2230 A normal use, 525-690 V 3-phase input, IP22, Type 1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145973 — Identification
ParameterValue
Frame size4xR8i+4xR8i
3AXD50000145973 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range48 ... 63 Hz
3AXD50000145973 — Output / Performance
ParameterValue
Output power, normal duty2200 kW
Output power, heavy duty1600 kW
Output power, light overload2000 kW
Output current, normal duty2230 A
Output current, heavy duty1668 A
Output current, light overload2141 A
Output power (UL), light overload2250 Hp
Output power (UL), heavy duty1750 Hp
Output current (UL), light overload2141 A
Output current (UL), heavy duty1668 A
3AXD50000145973 — Mechanical
ParameterValue
NEMA enclosure typeType1
3AXD50000145973 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP22

Product details

The ABB 3AXD50000145973 is rated for 2200 kW normal-use output power and 2230 A normal-use output current on a 525 to 690 V three-phase supply. It is a frame 4xR8i+4xR8i unit with the control module included, built for applications that need to feed regenerated energy back into the line rather than dump it across a brake resistor.

Normal-use output current is 2230 A, with a corresponding heavy-duty rating of 1668 A and a light-overload rating of 2141 A. The heavy-duty figure governs continuous motor load in a constant-torque application; the light-overload figure covers variable-torque loads like pumps and fans where occasional overload is expected. Apparent power output sits at 2665 kV·A, which gives you the transformer or generator sizing number for the line side. Input voltage range is 525 to 690 V AC, three-phase, 48 to 63 Hz. Maximum ambient temperature is 40 °C, altitude 1000 m without derating.

The drive carries 4 analog inputs and 4 analog outputs, plus 14 digital I/O and 10 digital outputs. The battery pack is two BR2032 lithium coins, 3 V each, 200 mAh — keep spares on the shelf for the control board memory backup.

Regulatory notes

The SCIP number is 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland, which is the EU waste framework declaration for the article. WEEE category is 4 (Large Equipment). The regenerative design is exempt from EU ecodesign efficiency requirements under Regulation EU/2019/1781 §2.3.c, so no energy-efficiency class is published for this drive.

Frequently asked questions

What are the key ratings of this drive?

Normal-use output is 2200 kW and 2230 A. Heavy-duty output is 1600 kW and 1668 A. Light-overload output is 2000 kW and 2141 A. Input is 525-690 V three-phase, 48-63 Hz.

What enclosure and protection rating does this drive have?

IP22 with a NEMA Type 1 enclosure. Indoor installation only, maximum ambient 40 °C, altitude 1000 m without derating.

What communication protocols does this drive support?

CAN communication is built in. There are no Industrial Ethernet interfaces on this variant; optional fieldbus adapters are required for PROFINET, EtherNet/IP, or similar protocols.

What is the SCIP number for this drive?

SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland. WEEE category is 4 (Large Equipment).

MPN
3AXD50000145973