ABB 3AXD50000145997 — AC Drive (VFD) 600V

ABB 3AXD50000145997 ACS880-17 Drive, 3200 kW, 3310 A

MPN3AXD50000145997
Active

ABB ACS880-17, 3AXD50000145997, regenerative drive, 3200 kW normal-use output, 3310 A normal-use current, 525-690 V input, IP22 enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145997 — Identification
ParameterValue
Frame size6xR8i+6xR8i
3AXD50000145997 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range48 ... 63 Hz
3AXD50000145997 — Output / Performance
ParameterValue
Output power, normal duty3200 kW
Output power, heavy duty2400 kW
Output power, light overload3000 kW
Output current, normal duty3310 A
Output current, heavy duty2476 A
Output current, light overload3178 A
Output power (UL), heavy duty2700 Hp
Output current (UL), light overload3178 A
Output current (UL), heavy duty2476 A
3AXD50000145997 — Mechanical
ParameterValue
NEMA enclosure typeType1
3AXD50000145997 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP22

Product details

Duty ratings that matter for your application

The 3AXD50000145997: Normal-use output (PN) is 3200 kW at 3310 A; for heavy-duty cycles the drive delivers 2400 kW at 2476 A (IhD), and for light-overload use it provides 3000 kW at 3178 A (IlD). The apparent power rating is 3956 kVA. These figures let you match the drive to the load profile — heavy-duty for constant-torque or high-starting-torque applications, light-overload for variable-torque loads like pumps and fans.

Enclosure, protection, and mounting

The drive is housed in a NEMA Type 1 enclosure with IP22 protection, suitable for indoor installation where falling dirt and dripping water are the main concerns. Frame size is 6xR8i+6xR8i — a large multi-cabinet configuration that requires floor space and proper ventilation. The unit includes four analog inputs and four analog outputs, plus 14 digital inputs and 10 digital outputs for control and feedback wiring.

Compliance and environmental notes

The drive is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c) because it is a regenerative drive — energy efficiency data is not provided. SCIP number is 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland. The unit contains two lithium coin cells (BR2032, 3V, 200 mAh each) for backup. Operating humidity range is 5-95% RH. The WEEE category is 4 (Large Equipment, any external dimension more than 50 cm).

Frequently asked questions

What are the key ratings of the 3AXD50000145997?

Normal-use output is 3200 kW at 3310 A; heavy-duty output is 2400 kW at 2476 A; light-overload output is 3000 kW at 3178 A. Input voltage is 525-690 V three-phase at 48-63 Hz.

What is the SCIP number for this drive?

The SCIP number is 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland.

Does the drive include a control unit?

Yes, the control unit is included with the drive.

MPN
3AXD50000145997