The 3AXD50000146192: The 430 A normal-use current (In) and 400 kW output power (Pn) define the continuous duty envelope for a standard motor load. Light-overload use sits at 420 A and 400 kW, splitting the difference. The UL listing confirms 370 A heavy-duty (350 Hp) and 420 A light-overload (450 Hp), so the drive carries the same ratings under UL evaluation. Input voltage spans 525 to 690 V at 48 to 63 Hz, three-phase. The apparent power output is 514 kV·A, which gives a headroom check for transformer or generator sizing. Enclosure is IP22 with NEMA Type 1 — drip-proof, indoor, no washdown. Ambient limit is 40 °C maximum; altitude ceiling is 1000 m without derating.
I/O and interfaces
The drive includes the control unit. It carries 2 analog inputs, 2 analog outputs, 7 digital inputs, and 5 digital outputs. Communication is CAN-based; there is no onboard Industrial Ethernet interface. Two CR2032 lithium coin cells back up the real-time clock and parameter storage.
SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A (Finland). The drive is exempt from EU ecodesign energy-efficiency requirements under Regulation EU/2019/1781 §2.3.d because it is a low-harmonic type. WEEE category 4 (large equipment). Sound level is 77 dB(A).