Skip to main content
ABB 3AXD50000158966 — AC Drive (VFD) 600V

ABB 3AXD50000158966 ACS880-04F Drive Module, 500 kW, 522 A

MPN3AXD50000158966
Active

ABB ACS880-04F-522A-7, LV AC industrial flange-mounted single drive module, IEC: Pn 500 kW, 522 A, 690 V, UL: Pld 500 Hp, 505 A, 575 V, R11 frame, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000158966 — Identification
ParameterValue
Frame sizeR11
3AXD50000158966 — Electrical (input)
ParameterValue
Input voltage range525 ... 690 V
Number of phases3-phase
Frequency range47.5 ... 63 Hz
3AXD50000158966 — Output / Performance
ParameterValue
Output power, normal duty500 kW
Output power, heavy duty450 kW
Output power, light overload500 kW
Output current, normal duty522 A
Output current, heavy duty455 A
Output current, light overload505 A
Efficiency level (IE class)IE2
Output power (UL), light overload500 Hp
Output power (UL), heavy duty450 Hp
Output current (UL), light overload505 A
Output current (UL), heavy duty455 A
3AXD50000158966 — Mechanical
ParameterValue
Mounting typeModule
NEMA enclosure typeOpen Type
3AXD50000158966 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP20

Product details

The 3AXD50000158966: R11 frame size, module mounting. Open-type NEMA enclosure with IP20 finger-safe protection. Ambient temperature max 40 °C; altitude rated to 4000 m without derating. Standby loss sits at 438 W; full-load power consumption is 5982 W.

Two analog inputs and two analog outputs on board. Six digital inputs and two digital outputs. CAN protocol for drive-to-drive or fieldbus communication. No onboard industrial Ethernet interface.

Frequently asked questions

What is the SCIP number for this drive module?

SCIP number e7d01a07-ae61-49b4-b4bb-74f563632932 Finland.

What is the altitude rating?

Rated for operation up to 4000 m altitude.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). UL ratings provided for heavy-duty and light-overload use.

What are the normal-use power ratings?

500 kW output power at 522 A, 525...690 V input, three-phase.