Duty ratings and application fit
The 3AXD50000158997: Three overload profiles are defined: normal use (Pn 710 kW, In 721 A), light-overload (PlD 630 kW, IlD 705 A), and heavy-duty (PhD 560 kW, IhD 571 A). The heavy-duty current matches the UL listing at 571 A / 600 Hp. For a 690 V line, the 862 kV·A apparent power rating frames the transformer or generator sizing. Standby loss sits at 438 W; full-load power consumption is 9617 W. Efficiency class IE2 is declared.
Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. No industrial Ethernet interface — communication is via CAN. A lithium coin cell (CR2032, 220 mAh) pair backs up the real-time clock and parameter storage. The module is flange-mounted, intended for panel integration where the R11 frame size and IP20 dictate cabinet layout.