The ABB 3AXD50000162055 is a frame R4 variable-frequency drive rated for 11 kW normal-use output at 48.0 A, with a heavy-duty rating of 7.5 kW at 32.0 A. Input is 200-240 V three-phase, 47.5-63 Hz. Built-in MODBUS RTU on the RS-485 port; no industrial Ethernet interface on this variant. Ambient limit is 50 °C maximum, derating above 40 °C per the thermal curve. IP20 enclosure, NEMA Open Type — intended for cabinet mounting where the surrounding enclosure provides splash and dust protection. Efficiency class IE2, power factor 0.98 at rated load. Standby loss 35 W, full-load consumption 561 W.
Analog inputs: 2. Analog output: 1. Digital I/O: 5 inputs, 2 outputs. The control unit is included in the package — no separate ordering of a control panel or adapter needed for basic operation. MODBUS RTU at 19200 baud default; DIP-switch selectable for 9600. No fieldbus option card slot is documented for this order code — the serial port is the only external communication path.
Module mounting, frame R4. Altitude rating 1000 m without derating. Operating humidity 5-95% non-condensing. Sound level 69 dB(A) — typical for a fan-cooled drive at this power level. No battery included.