Skip to main content
ABB 3AXD50000268498 — AC Drive (VFD) 240V

ABB 3AXD50000268498 ACQ580-01 VFD, 143 A, 230 V

MPN3AXD50000268498
Active

ABB ACQ580-01 wall-mount VFD, frame R6, 3-phase 208–240 V input, 143 A light-overload (50 Hp), 40 A heavy-duty (40 Hp), 57 kVA, IP21, Type 1, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Input

3AXD50000268498 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz

Electrical Output

3AXD50000268498 — Electrical Output
ParameterValue
Output power, heavy duty (UL, Hp)40 Hp
Output current, heavy duty (UL)40 A
Apparent power output57 kV·A
Output power, light-overload duty (UL, Hp)50 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)143 A
Standby loss22 W

Environmental

3AXD50000268498 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C

Mechanical

3AXD50000268498 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR6
Mounting typeWall-mounting

Product details

The ABB 3AXD50000268498 is an ACQ580-01 wall-mount VFD in frame R6, built for water and wastewater duty on 208–240 V three-phase supply. Light-overload rating hits 143 A (50 Hp), heavy-duty drops to 40 A (40 Hp) — that 143 A figure is the one you size branch feeders for when the pump runs continuous. Apparent power output is 57 kVA. Enclosure is IP21 / NEMA Type 1, so it's indoor panel or wall-mount only; keep ambient under 40 °C. Standby loss sits at 22 W — negligible for the cabinet heat budget, but counts if you're on a UPS-backed control power bus.

Frame R6 is the physical envelope — determines gland plate layout, DIN-rail or backplate drilling, and whether it fits a 600 mm wide cabinet. Wall-mounting is standard; no floor-standing kit needed. The 143 A light-overload curve is for variable-torque loads (pumps, fans) where the drive rarely sees peak current for more than a minute. Heavy-duty 40 A is for constant-torque applications (conveyors, positive-displacement pumps) at full rated current. If your motor FLA sits between 40 and 143 A, you're in the light-overload zone — just confirm the motor's service factor and the drive's thermal model match. IE2 efficiency class means it meets the EU minimum for this power band; no premium-efficiency premium to pay.

Frequently asked questions

What is the frame size of this drive?

Frame R6. That determines the physical mounting footprint and the gland plate layout for incoming power and motor cables.

What is the standby power loss?

22 W. That's the heat the drive dissipates when the motor is stopped but the DC bus is still energized — relevant for cabinet cooling calculations and UPS sizing.

What compliance documentation is available for this drive?

The drive carries a UL listing (UL/cUL) as standard for the ACQ580-01 series, and it's CE-marked for the European market. RoHS and REACH declarations are part of ABB's standard documentation package for this product line. WEEE category is 4 (Large Equipment).

MPN
3AXD50000268498