Skip to main content
ABB 3AXD50000268627 — AC Drive (VFD) 600V

ABB 3AXD50000268627 ACQ580-01-041A-6 Drive, 40 HP, 41 A, 575

MPN3AXD50000268627
Active

ABB ACQ580-01-041A-6 wall-mounted LV AC drive, frame R5, 3-phase 500-600 V input, IP21, NEMA 1, UL rated 40 Hp light-overload / 30 Hp heavy-duty at 575 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000268627 — Identification
ParameterValue
Frame sizeR5
3AXD50000268627 — Electrical (input)
ParameterValue
Input voltage range500 ... 600 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000268627 — Output / Performance
ParameterValue
Output power (UL), light overload40 Hp
Output power (UL), heavy duty30 Hp
Output current (UL), light overload41 A
Output current (UL), heavy duty30 A
3AXD50000268627 — Mechanical
ParameterValue
Mounting typeWall-mounting
NEMA enclosure typeType1
3AXD50000268627 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP21

Product details

The ABB 3AXD50000268627 is an ACQ580-01-041A-6 wall-mounted drive in frame R5, built for LV AC motor control in water and wastewater applications. It takes a 3-phase 500-600 V input and delivers UL-rated output: 30 A / 30 Hp heavy-duty, or 41 A / 40 Hp light-overload at 575 V. The enclosure is IP21 with NEMA Type 1, so it's fine for indoor, clean-ish environments — no washdown, no dust.

Wall-mount, frame R5, IP21 — means you need a solid backplate and some clearance around it for airflow. The NEMA 1 enclosure is basically a ventilated box, so keep it out of dripping pipes and direct spray. Input side is 500-600 V three-phase; no autotransformer needed if your plant runs 480 or 575 V. The heavy-duty rating (30 A) is what governs for constant-torque loads like screw pumps or aerators; light-overload (41 A) works for variable-torque pumps and fans where the peak is only during startup.

Frequently asked questions

What is the frame size of this drive?

It's frame R5, which is a standard ABB drive frame size for this power class.

What frequency does this drive support?

It's rated for 50/60 Hz input, so it works on either 50 Hz or 60 Hz mains without derating.

What compliance documentation is available for this drive?

The drive carries UL listing (evident from the UL output ratings) and is WEEE Category 4 (Large Equipment). RoHS/REACH documentation should be available from ABB's standard compliance portal for this active product family.

MPN