Skip to main content
ABB 3AXD50000268689 — AC Drive (VFD) 600V

3AXD50000268689 ACQ580-01-144A-6 LV AC Drive, R8, 144 A, 125

MPN3AXD50000268689
Active

ABB ACQ580-01 LV AC wall-mounted drive, frame R8, 500–600 V 3-phase input, 144 A light-overload UL output, 125 A heavy-duty UL output, IP21, NEMA Type1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000268689 — Identification
ParameterValue
Frame sizeR8
3AXD50000268689 — Electrical (input)
ParameterValue
Input voltage range500 ... 600 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000268689 — Output / Performance
ParameterValue
Output power (UL), light overload150 Hp
Output power (UL), heavy duty125 Hp
Output current (UL), light overload144 A
Output current (UL), heavy duty125 A
3AXD50000268689 — Mechanical
ParameterValue
Mounting typeWall-mounting
NEMA enclosure typeType1
3AXD50000268689 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP21

Product details

The ABB 3AXD50000268689 is the order code for an ACQ580-01-144A-6 LV AC drive in frame R8. It takes a 500–600 V 3-phase input and delivers 144 A continuous under light-overload UL duty (150 Hp at 575 V) or 125 A under heavy-duty UL duty (125 Hp). The enclosure is IP21, NEMA Type1, wall-mounted — sized for water/wastewater installations where the drive sits in a controlled indoor space, not washdown.

The UL heavy-duty rating of 125 A (125 Hp) governs continuous motor operation at full rated load — the figure to match against your motor nameplate FLA for pump/fan duty. The light-overload rating of 144 A (150 Hp) allows a higher sustained current but with a shorter overload profile; use it when the drive is oversized for the motor to handle occasional surge, not constant full load. Both are UL-listed, so the drive qualifies for North American panel builds without derating gymnastics.

Wall-mounting with IP21 and NEMA Type1 means the drive is intended for indoor, non-condensing environments — clean electrical rooms or pump stations, not outdoor pads or washdown zones. The R8 frame is a larger chassis; verify wall clearance for heat sink airflow and cable bend radius before layout.

Frequently asked questions

What is the frame size of this drive?

Frame size R8.

What input voltage and frequency does it accept?

500–600 V 3-phase, 50/60 Hz.

What enclosure protection does it have?

IP21, NEMA Type1 — suitable for indoor, non-washdown environments.

MPN
3AXD50000268689