Skip to main content
ABB 3AXD50000270903 — AC Drive (VFD) 240V

3AXD50000270903 ABB ACS580-01-075A-2 25 Hp Drive, 208-240 V,

MPN3AXD50000270903
Active

ABB ACS580-01-075A-2, 3AXD50000270903, LV AC general-purpose wall-mounted drive, 25 Hp / 74.8 A light-overload, 20 Hp / 59.4 A heavy-duty, 208–240 V 3-phase, R4 frame, IP21, IE2, active.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000270903 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz
3AXD50000270903 — Electrical Output
ParameterValue
Output power, heavy duty (UL, Hp)20 Hp
Output current, heavy duty (UL)59.4 A
Apparent power output30 kV·A
Output power, light-overload duty (UL, Hp)25 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)74.8 A
Standby loss17 W
3AXD50000270903 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
3AXD50000270903 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR4
Mounting typeWall-mounting

Product details

The ABB 3AXD50000270903 is an ACS580-01-075A-2 general-purpose wall-mounted drive for 208–240 V 3-phase input. It delivers 25 Hp at 74.8 A under light-overload duty (variable-torque loads like fans and pumps) and 20 Hp at 59.4 A under heavy-duty use (constant-torque loads like conveyors). The R4 frame size and IP21 enclosure suit indoor panel mounting; standby loss sits at 17 W, a figure to include in enclosure thermal calculations.

The heavy-duty UL rating (20 Hp, 59.4 A) is the limiting spec for continuous constant-torque applications. If your load profile is variable torque — centrifugal pump, fan, compressor — the light-overload rating (25 Hp, 74.8 A) applies, giving 25% more headroom. Both ratings are at 40 °C ambient; derate above that per the thermal curve in the manual.

Mounting and compliance notes

Wall-mounting, IP21, NEMA Type 1 — indoor use only, no washdown. The 17 W standby loss is continuous; factor it into enclosure cooling if the cabinet is sealed. IE2 efficiency level meets baseline requirements for regions without mandatory IE3 legislation. The 50/60 Hz rating covers both line frequencies without derating.

Frequently asked questions

What is the listed frame size (R4) on this drive?

The frame size is R4, which determines the physical footprint and mounting hole pattern for panel layout.

What is the standby loss of this drive?

Standby loss is 17 W. This is the continuous heat dissipation when the drive is powered but not running a motor, and it should be included in enclosure thermal sizing.

What compliance documentation does ABB provide for this drive?

The drive carries UL listing (UL ratings are cited for heavy-duty and light-overload use) and is marked for 50/60 Hz operation. WEEE category 4 applies for end-of-life disposal. RoHS and REACH declarations are available through ABB's documentation portal.

MPN