Skip to main content
ABB 3AXD50000270996 — AC Drive (VFD) 240V

ABB 3AXD50000270996 ACS580-01 Wall Drive, 40 Hp, 114 A

MPN3AXD50000270996
Active

ABB ACS580-01 series, LV AC general-purpose wall-mounted drive, 3AXD50000270996, 40 Hp light-overload, 114 A, 240 V, Frame R5.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Input

3AXD50000270996 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz

Electrical Output

3AXD50000270996 — Electrical Output
ParameterValue
Output power, heavy duty (UL, Hp)30 Hp
Output current, heavy duty (UL)88 A
Apparent power output45 kV·A
Output power, light-overload duty (UL, Hp)40 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)114 A
Standby loss19 W

Environmental

3AXD50000270996 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C

Mechanical

3AXD50000270996 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR5
Mounting typeWall-mounting

Product details

The ABB 3AXD50000270996 is an ACS580-01-114A-2 LV AC general-purpose wall-mounted drive. It delivers 40 Hp (light-overload) at 114 A on a 208–240 V three-phase input, with a heavy-duty rating of 30 Hp at 88 A. Frame size R5, IP21 enclosure, NEMA Type 1.

Rated for 45 kV·A apparent output power, this drive handles a 30 Hp motor in heavy-duty cycles (constant torque, high starting loads) and 40 Hp in light-overload (variable torque, fans, pumps). The 88 A heavy-duty current and 114 A light-overload current define the thermal limit for continuous operation at 40 °C ambient. Standby loss is 19 W — relevant for panel heat load calculations when the motor is stopped but the drive remains powered. IE2 efficiency class applies; for applications requiring IE3 or IE4, confirm the motor match separately.

Wall-mounting, IP21, NEMA Type 1. Suitable for indoor, non-condensing environments. The R5 frame is a larger cabinet-style unit — plan for adequate clearance around the gland plate for incoming power and motor cables. Rated for 50/60 Hz supply; the 208–240 V input range covers common North American low-voltage three-phase networks.

Frequently asked questions

What is the frame size of this drive?

Frame size R5.

What is the standby loss?

19 W.

What compliance documentation is available?

The drive carries UL listing (UL ratings are provided for heavy-duty and light-overload use) and is WEEE Category 4. Full RoHS/REACH declarations are available from ABB on request.

MPN