It runs on a 3-phase 208-240 V supply, delivers 2 Hp under UL light-overload duty at 7.5 A output, and sits in Frame Size R1.
The UL light-overload rating of 2 Hp and 7.5 A defines the continuous motor capacity for typical HVAC fan and pump loads. The apparent power output is 3.0 kV·A. Standby loss is 13 W, which matters for thermal budgeting in enclosed panels — that's the heat the drive dissipates when the motor is stopped but the control electronics remain powered. Maximum ambient temperature is 40 °C — above that, output current must be derated per the drive's thermal curve.