The 3AXD50000284894: The light-overload rating (60 Hp, 169 A) is the number to match against your fan or pump motor FLA — not the drive's absolute maximum. This is the continuous current the drive can supply without derating for a variable-torque load. Standby loss sits at 22 W, so the cabinet ventilation budget needs to account for that even when the motor is stopped. Efficiency is IE2, which is the baseline for HVAC drives in most markets. The 40 °C maximum ambient is standard for a wall-mounted unit; if your machine room runs hotter, you'll need to derate or add forced airflow.
ABB 3AXD50000284894 ACH580-01 HVAC Drive, 60 Hp, 169 A, R7
ABB ACH580-01 wall-mounted HVAC drive, 3-phase 208-240 V, 60 Hp light-overload (169 A), 67 kVA, Frame R7, IP21, NEMA 1, IE2.
Specifications
Electrical Input
| Parameter | Value |
|---|---|
| Input voltage range | 208 ... 240 V |
| Number of phases | 3-phase |
| Frequency | 50/60 Hz |
Electrical Output
| Parameter | Value |
|---|---|
| Apparent power output | 67 kV·A |
| Output power, light-overload duty (UL, Hp) | 60 Hp |
| Efficiency class (IE) | IE2 |
| Output current, light-overload duty (UL) | 169 A |
| Standby loss | 22 W |
Environmental
| Parameter | Value |
|---|---|
| Temperature rating, max. | Maximum 40 °C |
Mechanical
| Parameter | Value |
|---|---|
| Degree of protection (IP) | IP21 |
| Enclosure type (NEMA) | Type1 |
| Frame size | R7 |
| Mounting type | Wall-mounted |
Product details
Frequently asked questions
What is the frame size of this drive?
Frame R7. That determines the physical footprint, mounting hole pattern, and the heat sink dimensions for cabinet layout.
What is the standby loss?
22 W. This is the power the drive consumes when the motor is stopped but the control electronics remain powered. It factors into cabinet heat load and energy cost calculations.
What are the key electrical ratings?
Input 208-240 V three-phase, 50/60 Hz. Light-overload output is 60 Hp at 169 A, with 67 kVA apparent power. Enclosure is IP21, NEMA Type 1.