Specifications

3AXD50000301881 — Identification
ParameterValue
Frame sizeR2
3AXD50000301881 — Electrical (input)
ParameterValue
Input voltage range500 ... 600 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000301881 — Output / Performance
ParameterValue
Output power, light overload7.5 Hp
Output current, normal duty9 A
3AXD50000301881 — Mechanical
ParameterValue
Mounting typeWall-mounting
NEMA enclosure typeType12
3AXD50000301881 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP55

Product details

The ABB 3AXD50000301881 is an ACH580-01-09A0-6+B056 LV AC wall-mounted drive built for HVAC duty. It delivers 9 A continuous output (normal use) on a 500-600 V three-phase input, with a light-overload rating of 7.5 Hp. The IP55 / NEMA Type12 enclosure suits it for washdown or dusty environments without a separate cabinet. Frame size R2 keeps the footprint compact for wall-mounting.

The 9 A normal-use output current is the continuous rating at 50/60 Hz — this is the number to match against your motor FLA, not the 7.5 Hp light-overload figure. The light-overload 7.5 Hp applies for variable-torque loads (fans, pumps) where the drive can deliver higher current for short periods. Input voltage range of 500-600 V covers 480 V and 575 V nominal systems; confirm your supply phase-to-phase voltage falls within that band. The IP55 / NEMA Type12 enclosure means the drive is sealed against dust and low-pressure water jets — no need for an additional enclosure in most indoor HVAC mechanical rooms, but outdoor installation still requires a weather hood.

Frequently asked questions

What is the frame size of this drive?

Frame size R2. This determines the physical mounting footprint and the available options slot configuration.

What input voltage and frequency does it accept?

Three-phase 500-600 V at 50/60 Hz. The 9 A output current is rated at these nominal conditions.

What enclosure protection does it have?

IP55 and NEMA Type12. Suitable for indoor environments with dust and moisture, without an additional cabinet.

MPN