The 3AXD50000417353: The 6.7 A normal-use output (In) is the continuous current the drive can supply to a standard variable-torque load (pumps, fans) without derating. For constant-torque or high-starting-torque applications (conveyors, compressors), the heavy-duty rating of 4.6 A (IhD) is the limiting figure — size the motor and cable accordingly. The 200–240 V input range covers common single-phase and three-phase supplies in North America and parts of Asia; the 47.5–63 Hz frequency tolerance handles weak grids or generator-fed installations. Standby loss of 13 W and power consumption of 72 W at rated load give a baseline for panel thermal budgeting. Efficiency class IE2 is the baseline for this drive size; it meets the minimum efficiency requirements for most general-purpose applications without premium IE3 hardware. The 59 dB(A) sound level is moderate — acceptable for machine-mounted or panel-enclosed installations, but noticeable in a quiet control room.
Integration notes
The drive includes a control unit and provides 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for basic speed reference, start/stop, and status feedback without an expansion module. Communication is via CAN protocol; there are no industrial Ethernet interfaces on this variant, so plan for a separate fieldbus adapter if Ethernet connectivity is required. The lithium coin cell (CR2032, 220 mAh) backs up the real-time clock and parameter storage; it is field-replaceable. Wall-mount the R1 frame with clearance for the IP21 enclosure's cooling airflow; derate above 40 °C ambient and above 1000 m altitude.