Skip to main content
ABB 3AXD50000417391 — AC Drive (VFD) 240V

ABB 3AXD50000417391 ACS580-01 drive, 5.5 kW, 24.5 A, 230 V

MPN3AXD50000417391
Active

ABB ACS580-01 series, LV AC general purpose wall-mounted drive, 3AXD50000417391, 5.5 kW / 24.5 A, 230 V, IP21, Type 1.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417391 — Electrical Output
ParameterValue
Output power, normal duty (Pn)5.5 kW
Output current, normal duty (In)24.5 A
Output power, heavy duty (PhD)4.0 kW
Output current, heavy duty (IhD)16.7 A
Output power, light-overload duty (PlD)5.5 kW
Output current, light-overload duty (IlD)24.2 A
Apparent power output9.8 kV·A
Efficiency class (IE)IE2
Standby loss14 W
Power consumption255 W

Electrical Input

3AXD50000417391 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417391 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417391 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity5 ... 95
Altitude1000 m
Noise level64 dB(A)

Mechanical

3AXD50000417391 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR2
Mounting typeWall-mounted

Approvals

3AXD50000417391 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The 3AXD50000417391: Frame size R2, IP21 with NEMA Type 1 enclosure, wall-mounted. The standby loss of 14 W matters for panel heat calculations if you are stacking multiple drives in a sealed cabinet. Communication is CAN-based, with 6 digital inputs and 3 digital outputs plus 2 analog inputs and 2 analog outputs. No onboard Ethernet — if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter module.

Installation notes

Mount on a flat vertical surface; the wall-mounted frame R2 accepts cable entry from the bottom. Operating ambient max 40 °C, humidity 5...95 % non-condensing. Sound level 64 dB(A) at full load — audible in a quiet control room, so factor in enclosure attenuation if noise is a concern. The drive includes a control unit and a lithium coin cell CR2032 (220 mAh, 3 V) for real-time clock backup. Replace during scheduled maintenance; the cell is standard and widely available.

Frequently asked questions

What compliance documentation does this drive provide?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 8e2f57c3-6325-4d67-b705-81477a8d922e Finland.

What are the key ratings for normal and heavy-duty use?

Normal use: 5.5 kW output power, 24.5 A output current. Heavy-duty use: 4.0 kW output power, 16.7 A output current. Light-overload use: 5.5 kW output power, 24.2 A output current.

What is the input voltage and frequency range?

Input voltage 200...240 V three-phase, frequency 47.5...63 Hz.

MPN
3AXD50000417391