Output ratings and duty selection
The 3AXD50000417407: Normal-use output is 7.5 kW at 31.2 A; heavy-duty use drops to 5.5 kW at 24.2 A. Light-overload use matches the normal-use power at 7.5 kW but current is slightly lower at 30.8 A.
Input and environment
Runs on 200-240 V three-phase, 47.5-63 Hz. Ambient temperature max is 40 °C, with 5-95% non-condensing humidity. Altitude rating is 1000 m — above that you'll need to derate output current per the manual. Standby loss is 14 W; full-load power consumption is 359 W. Acoustic noise is 64 dB(A) — noticeable in a quiet control room but fine on a plant floor.
Built-in I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is CAN-based — no onboard Ethernet, so if you need Modbus TCP or PROFINET you'll need an optional fieldbus adapter. The control unit is included in the package.