Duty ratings that matter for motor matching
The 3AXD50000417414: Normal-duty output is 11 kW at 46.7 A — that's your everyday pump/fan curve. Light-overload use sits at 11.0 kW and 46.2 A, nearly identical to normal duty but with a different overload profile; check the drive's parameter set if you're pushing the overload cycle.
Frame size R3, wall-mounted, IP21 enclosure with NEMA Type 1 equivalency. Ambient temp max 40 °C, altitude 1000 m — derate above that. Standby loss is 15 W, so the panel's thermal budget can treat it as a minor heat source. Sound level 76 dB(A) — noticeable in a quiet control room, fine on the plant floor.
Two analog inputs, two analog outputs, six digital inputs, three digital outputs. Communication is CAN — no onboard Industrial Ethernet, so if the line talks PROFINET or EtherNet/IP, you'll need an add-on module. The control unit is included; no separate order needed.