ABB 3AXD50000417452 — AC Drive (VFD) 240V

ABB 3AXD50000417452 ACS580-01-144A-2 Drive, 37 kW, 144 A

MPN3AXD50000417452
Active

ABB ACS580-01 general-purpose wall-mounted drive, order code 3AXD50000417452, 37 kW normal-use output, 144 A, 230 V input, frame size R6.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417452 — Electrical Output
ParameterValue
Output power, normal duty (Pn)37 kW
Output current, normal duty (In)144 A
Output power, heavy duty (PhD)30.0 kW
Output current, heavy duty (IhD)114 A
Output power, light-overload duty (PlD)37 kW
Output current, light-overload duty (IlD)143 A
Apparent power output57 kV·A
Efficiency class (IE)IE2
Standby loss22 W
Power consumption1932 W

Electrical Input

3AXD50000417452 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417452 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417452 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity5 ... 95
Altitude1000 m
Noise level67 dB(A)

Mechanical

3AXD50000417452 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR6
Mounting typeWall-mounted

Approvals

3AXD50000417452 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

Drive rating and duty selection

The ABB 3AXD50000417452 is the ACS580-01-144A-2, a general-purpose wall-mounted drive rated for 37 kW normal-use output at 144 A on a 200...240 V three-phase supply. Heavy-duty use drops to 30.0 kW at 114 A, while light-overload use holds at 37 kW with 143 A — the normal and light-overload curves overlap, so the heavy-duty figure is the one that governs for constant-torque loads like conveyors or positive-displacement pumps. Apparent power output sits at 57 kV·A, and standby loss is 22 W — relevant for panel heat budgeting when the drive is idle but powered. Efficiency class is IE2, in line with the current EU Ecodesign requirements for this power band.

Frame size R6, wall-mounted, IP21 with NEMA Type 1 enclosure. Ambient temperature max 40 °C, altitude 1000 m without derating; above that, standard drive derating applies. Operating humidity 5...95% RH non-condensing. Sound level is 67 dB(A) — noticeable in a quiet control room but typical for an R6 frame at full load. The drive includes the control unit, so no separate controller module to order.

Onboard I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is via CAN; there are no industrial Ethernet interfaces built in — if you need PROFINET or EtherNet/IP, that requires an optional fieldbus adapter module. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock and parameter backup alive during power-down.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 37 kW at 144 A; heavy-duty use is 30.0 kW at 114 A; light-overload use is 37 kW at 143 A. Input voltage is 200...240 V three-phase.

What compliance documentation does ABB provide for this drive?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances > 0.1 mass percentage (date 20250905). SCIP number c9f22bb1-0f1d-4f56-a642-05f2b82ea395 Finland is registered.

What is the enclosure type and mounting?

IP21 / NEMA Type 1, wall-mounted. Suitable for indoor, dry environments. Ambient temperature max 40 °C, altitude 1000 m without derating.

MPN
3AXD50000417452