Output ratings and duty selection
The 3AXD50000417506: Normal-use (light-overload) output is 1.1 kW at 6.6 A; heavy-duty use derates to 0.75 kW at 4.6 A. That means for a constant-torque load like a conveyor or positive-displacement pump, size against the heavy-duty column. For variable-torque fans and centrifugal pumps, the normal-use figure applies. The IE2 efficiency level is standard for this power band.
IP55 / NEMA 12 enclosure, wall-mounted, R1 frame. Rated for ambient up to 40 °C and 95 % RH non-condensing. Standby loss is 13 W; total power consumption at rated load is 72 W.
Two analog inputs, two analog outputs. Six digital inputs and three digital outputs. Communication is CAN-based; no onboard industrial Ethernet port. For a Modbus TCP or PROFINET network, an optional fieldbus adapter is required. The drive accepts 47.5–63 Hz line frequency.