Skip to main content
ABB 3AXD50000417537 — AC Drive (VFD) 240V

ABB 3AXD50000417537 ACS580-01-018A-2+B056 Drive, 4 kW, 16.9

MPN3AXD50000417537
Active

ABB ACS580-01 general-purpose wall-mounted drive, 3AXD50000417537, 4 kW normal-use output, 16.9 A, 200-240 V 3-phase, IP55, R1 frame, CAN interface.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417537 — Electrical Output
ParameterValue
Output power, normal duty (Pn)4 kW
Output current, normal duty (In)16.9 A
Output power, heavy duty (PhD)3.0 kW
Output current, heavy duty (IhD)10.6 A
Output power, light-overload duty (PlD)4.0 kW
Output current, light-overload duty (IlD)16.7 A
Apparent power output7.2 kV·A
Efficiency class (IE)IE2
Standby loss13 W
Power consumption230 W

Electrical Input

3AXD50000417537 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417537 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417537 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95

Mechanical

3AXD50000417537 — Mechanical
ParameterValue
Degree of protection (IP)IP55
Enclosure type (NEMA)Type12
Frame sizeR1
Mounting typeWall-mounted

Approvals

3AXD50000417537 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000417537 is an ACS580-01-018A-2+B056 general-purpose wall-mounted drive rated for 4 kW normal-use output at 16.9 A on a 200-240 V three-phase supply. Heavy-duty use drops to 3.0 kW and 10.6 A, so the normal-use figure governs the motor sizing for most constant-torque loads; the heavy-duty curve applies when ambient temperature or duty cycle pushes the thermal limit. The R1 frame size and IP55 enclosure with NEMA Type 12 rating mean this drive mounts directly on a wall or machine frame in dusty, washdown-adjacent environments — no separate cabinet needed for most food-and-bev or light industrial lines. Standby loss of 13 W keeps the panel heat load low when the motor is stopped.

The drive carries 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs — enough for basic speed reference, feedback, and start/stop control without an expansion module. Communication is CAN-based; there is no onboard industrial Ethernet port, so if the line uses PROFINET or EtherNet/IP, plan for an optional fieldbus adapter.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 2024-05-08). REACH confirms substances above 0.1% mass percentage. The SCIP number is 12216470-2923-46fb-9b3c-c7084d490da0 (Finland).

What is the normal-use output rating for this drive?

Normal-use (light-overload) output is 4 kW at 16.9 A. Heavy-duty use is 3.0 kW at 10.6 A. The normal-use figure governs motor sizing for constant-torque applications.

What enclosure rating does this drive have?

IP55 with NEMA Type 12, suitable for wall mounting in dusty or washdown-adjacent environments without a separate cabinet.

MPN
3AXD50000417537