This ABB ACH580-01-012A-2 (order code 3AXD50000417674) is a 3-phase, wall-mounted LV AC drive built for HVAC duty. It's rated 3 kW normal-use output at 12 A, with a 200-240 V input, and carries a heavy-duty rating of 2.2 kW at 7.5 A for tougher loads. Communication is handled over BACnet, making it a straight drop into most building management systems. The enclosure is IP21 / NEMA Type 1, so it's fine for indoor installs where dripping water or light dust might be present, but not for washdown areas.
The normal-use current of 12 A (at 3 kW) is the headline number for most fan and pump applications. The heavy-duty curve drops to 7.5 A at 2.2 kW — that's the rating to watch if the motor sees constant torque or intermittent overloads. Light-overload use sits at 11.8 A, close to the normal-use figure. Input voltage is 200-240 V, 3-phase. Frequency range is 47.5-63 Hz. Standby loss is 13 W — worth noting if the drive spends long periods idling. Sound level is 59 dB(A), typical for an R1 frame at full load. The drive includes the control unit, so no separate controller to order. It has 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs — enough for basic pressure, temperature, or flow control loops without an expansion module.
Wall-mounted, R1 frame size. Ambient temperature is rated to 40 °C maximum — keep the cabinet ventilated if it's in a warm mechanical room. Altitude derating starts above 1000 m. Operating humidity up to 95% RH, non-condensing. The internal battery is a CR2032 lithium coin cell (220 mAh, 3 V) for real-time clock backup.