The 3AXD50000417681: Normal-use output current (In) is 16.9 A — that's the continuous rating for a 4 kW motor on a standard fan or pump curve. Heavy-duty use (IhD) drops to 10.6 A at 3.0 kW, which governs constant-torque loads like conveyors or compressors. The drive carries an IE2 efficiency level, and standby loss is 13 W — relevant for continuous-running installations where idle power matters. Communication is BACnet over the built-in interface — no Industrial Ethernet port on this variant (0 hardware interfaces for that protocol). Analog I/O is 2 inputs and 2 outputs; digital I/O is 6 inputs and 3 outputs. The BACnet stack is preloaded, so no option card is needed for BMS integration.
Wall-mounted, frame size R1. Ambient temperature is rated to 40 °C maximum; altitude to 1000 m without derating. Sound level is 59 dB(A) — typical for this power class, not silent but acceptable in a mechanical room.