The 3AXD50000417698: Normal-use output current of 24.5 A (24.2 A light-overload) sets the motor FLA limit for continuous fan/pump duty. Heavy-duty 16.7 A is the hard ceiling for variable-torque loads that need occasional overload headroom — match that to the motor nameplate if the application cycles against a closed damper. Standby loss of 14 W and 255 W power consumption at rated load give the panel cooling calc a number to work with.
Two analog inputs, two analog outputs — enough for a speed reference and feedback transducer. Six digital inputs and three digital outputs cover start/stop, fault reset, and a run-status relay. No onboard Ethernet; BACnet rides on the serial RS-485 port. If the BMS expects BACnet/IP, you will need a fieldbus adapter.